BS 7671:2018 · 18th Edition · Table 41.1
Amendment 4 publishes 15 April 2026 — see what's changing →

Maximum disconnection times for protective devices

Maximum disconnection times from BS 7671:2018 Table 41.1. For automatic disconnection of supply to prevent electric shock. Times depend on system type (TN/TT), voltage, and circuit type (final/distribution).
Table 41.1 — Final circuit disconnection times
Maximum disconnection times (seconds)
Voltage
range
TN
AC
TN
DC
TT
AC
TT
DC
50–120V0.8N/R0.3N/R
120–230V0.45.00.20.4
230–400V0.20.40.070.2
>400V0.10.10.040.1
N/R = disconnection not required for protection against electric shock at this voltage.
Distribution circuit disconnection times
System type Max time (s)
TN systems5.0
TT systems1.0
Regulation 411.3.2.3 (TN) and 411.3.2.4 (TT).
Special locations (reduced times)
Location Max time (s)
Medical Group 20.1
Agricultural0.2
Section 710 (medical) and Section 705 (agricultural). Applies to both TN and TT systems.

RCD types — which to use and when

Type AC

Sinusoidal AC fault currents only

Basic RCD protection. Detects AC residual currents only. Being phased out in favour of Type A for most applications.

  • Older domestic installations
  • Purely resistive loads (heaters, filament lighting)
  • Not suitable for circuits with electronic equipment

Type A

Sinusoidal AC + pulsating DC fault currents

The standard RCD type for most modern installations. Detects AC and pulsating DC fault currents generated by electronic equipment.

  • LED drivers and electronic lighting
  • IT equipment and computers
  • EV chargers with onboard rectifiers (Mode 2)
  • Washing machines, dishwashers, induction hobs
  • Minimum requirement for most circuits per BS 7671

Type F

Composite frequencies up to 1kHz

For circuits supplying equipment that generates high-frequency fault currents. Extends Type A protection to composite frequencies.

  • Variable frequency drives (VFDs)
  • UPS systems
  • Inverter-driven equipment (heat pumps, air conditioning)

Type B

All fault current types including smooth DC

The most comprehensive RCD type. Detects all residual current waveforms including smooth DC. Required where DC fault currents can occur.

  • EV charging (Mode 3, dedicated circuits)
  • Solar PV systems with DC-side earth faults
  • Medical equipment (per Section 710)
  • Battery storage systems
  • BS EN 62423

Type S (Selective / Time-delayed)

Intentional time delay for discrimination

Not a sensitivity type but a time-delay variant. Used upstream to allow downstream RCDs to trip first, preventing nuisance tripping of the whole installation.

  • Main switch RCDs in split-load consumer units
  • Board incomers where multiple RCDs are downstream
  • Available in Type A and Type B variants
Table 41.5 — Max Zs for RCDs at 230V
Maximum earth fault loop impedance for RCDs to BS EN 61008 / BS EN 61009. Where an RCD provides fault protection, Zs must ensure the residual current operates the RCD.
IΔn Max Zs (Ω)
30 mA1667
100 mA500
300 mA167
500 mA100
For full max Zs tables for MCBs, fuses and MCCBs, see maxzs.co.uk

RCD sensitivity ratings — when to use each

10 mA

Additional protection — high-risk environments
  • Bathrooms and shower rooms (some specifications)
  • Medical locations (supplementary protection)
  • Construction sites (some specifications)
  • Rarely used in standard domestic installations

30 mA

General additional protection — the standard for most circuits
  • Socket outlets up to 32A (Reg 411.3.3)
  • Cables in walls at less than 50mm depth
  • Mobile equipment used outdoors
  • Bathrooms and swimming pools (Section 701, 702)
  • TT system final circuits
  • The default choice for domestic and commercial installations

100 mA

Fire protection
  • Distribution boards
  • Large installations where 30mA would cause nuisance tripping
  • Fire protection for cables (Reg 532.1)

300 mA

Fire protection — main distribution
  • Main distribution boards
  • Industrial installations
  • Fire protection where 100mA is impractical

500 mA

Fire protection — specialised equipment
  • Medical systems
  • Specialised industrial equipment
  • Large motor circuits

Table 41.1: Applies to automatic disconnection of supply for fault protection per Chapter 41 of BS 7671:2018.

TN systems: TN-S, TN-C-S (PME). TT systems: Own earth electrode.

120–230V AC: The most common voltage range for UK installations. 0.4s for TN final circuits, 0.2s for TT final circuits.

Amendment 4: Disconnection times unchanged in Amendment 4. See what is changing at bs7671amendment4.co.uk

Max Zs: Full tables for MCBs, fuses, and MCCBs at maxzs.co.uk

RCD Standards: BS EN 61008 (general RCD), BS EN 61009 (RCBO), BS EN 62423 (Type B), BS 4293 (industrial), BS 7288 (socket outlets).

RCD protection is validated automatically in PUG — certification software that checks every circuit against BS 7671.

Join the waitlist →